Part Number Hot Search : 
GC100 SEL1721Y 2A152 5262B 1040405 2SC2970 31M16 NTXV2N6
Product Description
Full Text Search
 

To Download HAZ6000-SRI Datasheet File

  If you can't view the Datasheet, Please click here to try to view without PDF Reader .  
 
 


  Datasheet File OCR Text:
 Current Transducers HAZ 4000..20000-SRI
For the electronic measurement of currents: DC, AC, pulsed, mixed, with a galvanic isolation between the primary circuit (high power) and the secondary circuit (electronic circuit).
IPN = 4000..20000 A IOUT = 0-20 mA (T-RMS DC)
Electrical data
Primary nominal r.m.s. current IPN (A) 4000 6000 10000 12000 14000 20000 Primary current measuring range IP (A) 4000 6000 10000 12000 14000 20000 Type
HAZ HAZ HAZ HAZ HAZ HAZ
4000-SRI 6000-SRI 10000-SRI 12000-SRI 14000-SRI 20000-SRI
Features
* Hall effect measuring principle * Galvanic isolation between primary * True-rms, 0-20mA DC current output * Isolation voltage 12kV Rms/ 50 Hz * Low power consumption * Package in PBT meeting UL 94-V0
/ 1 min and secondary circuit
VC IC IOC RIS IOUT ROUT RL
Supply voltage ( 5 %) Current consumption Overload capacity Isolation resistance @ 500 VDC Output current @ IPN, TA = 25C Output internal resistance Load resistance
15 V 50 mA 30,000 A > 1000 M 0-20 mA DC approx. 20 < 300
Advantages
* Easy mounting * Small size and space savings * Only one design for wide current * High immunity against external
interference ratings range
Accuracy - Dynamic performance data
X
L
IOE IOM IOT TC G tr f
Accuracy @ IPN, TA = 25C (without offset) Linearity error 1) (0 .. IPN) Electrical offset current, TA = 25C, @ IP = 0 Residual offset current @ IP = 0; after an excursion of 1 x IPN Thermal drift of IOE Thermal drift of the gain (% of reading) Response time @ 90% of IPN Frequency range, 3 dB, small signal 2)
<1 % < 0.5 % of IPN < 0.08 mA < 0.025 < 0.05%of < 0.05 < 400 mA
IPN/K
Applications
* Battery supplied applications * Uninterruptible Power Supplies * Power supplies for welding and
telecom applications. (UPS)
%/K ms
DC and 15 to 3kHz
General data
TA TS Ambient operating temperature Ambient storage temperature Housing PBT 30% glassfiber UL94 classification Mass Standards 3) - 25 .. + 85 - 30 .. + 90 C C
Application Domain
V0 approx. 6 kg EN 50178: 1997
m
* Industrial
Notes :
1) 2) 3)
Linearity data exclude the electrical offset. To avoid excessive core heating. Please consult characterisation report for more technical details and application advice. 060428/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Page 1/3
LEM
www.lem.com
Current Transducer HAZ 4000..20000-SRI
Isolation characteristics
Vb Nominal Voltage with IEC 61010-1 standard and following conditions - Single insulation - Over voltage category III - Pollution degree 2 - Heterogeneous field Nominal Voltage with EN 50178 standard and following conditions - Reinforced insulation - Over voltage category III - Pollution degree 2 - Heterogeneous field R.m.s. voltage for AC isolation test, 50/60 Hz, 1 mn R.m.s. voltage for partial discharge extinction @ 10pC Impulse withstand voltage 1.2/50s Creepage distance Clearance distance Comparative Tracking Index (Group IIIa) 2000 V r.m.s.
Vb
2000
V r.m.s.
Vd Ve Vw dCp dCl CTI
12 >3 27 > 45 > 45 220
kV kV kV mm mm V
060428/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice. Page 2/3
LEM
www.lem.com
Dimensions HAZ 4000..20000-SRI (in mm. 1 mm = 0.0394 inch)
FUJICON F2023A 6
1
Connection Circuit
HAZxxx-SRI
1 +Vc -Vc 0V OUTPUT GND RL< 300 Ohm
6
5
4
3
2
1
50
48
T.P.
GND OUTPUT
0V -Vc +Vc
HAZ 10000-SRI
250 +/-1.5 235
2 3
4-D6
4 5
160 +/-1.5 65
6
42 1.5 41.5 2 42 +/-1
T.P. (Internal test point used during factory calibrations)
125
162 1 161 162 +/-12
75
Operation Principle
7.5
+Vc
200 M5
Terminal 1...+Vc 2...-Vc 3...0V 4...OUTPUT 5...GND 6...T.P.
Output 0V Ip -Vc
50 48 35
General tolerance +/-0.5
Mechanical characteristics
* General tolerance * Aperture for primary conductor
0.5 mm 162 mm x 42 mm ( 2 mm) * Transducer fastening 4 x M5 (not supplied) * Recommended fastening torque < 5 Nm * Connection of secondary Fujicon F2023A (6 terminals)
Safety
This transducer must be used in electric/electronic equipment with respect to applicable standards and safety requirements in accordance with the following manufacturer's operating instructions.
Caution, risk of electrical shock When operating the transducer, certain parts of the module can carry hazardous voltage (eg. primary busbar, power supply). Ignoring this warning can lead to injury and/or cause serious damage. This transducer is a built-in device, whose conducting parts must be inaccessible after installation. A protective housing or additional shield could be used. Main supply must be able to be disconnected. 060428/4
Remarks
* Temperature of the primary conductor should not exceed
120C.
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
Page 3/3
LEM
www.lem.com


▲Up To Search▲   

 
Price & Availability of HAZ6000-SRI

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X